A cable fault, a generator that never started, and Google Cloud's London region goes dark

For about six hours, a power failure in one Google data center knocked out cloud services across its London region and rippled into UK banking apps. Google's own report traces it to a chain of small failures.

At about 7 a.m. London time on Tuesday, October 20, part of Google Cloud's europe-west2 region in London lost power. Services that businesses rent from Google, including virtual servers, databases and data tools such as BigQuery and Looker, stopped responding. Downdetector, a site that collects user problem reports, showed spikes for the UK banking apps Revolut and Lloyds Bank, as well as the property site Rightmove and the delivery firm DPD.

Google's incident report reads like a run of bad luck. An underground cable fault cut the facility's utility feed while its second feed was already switched off for repairs. The backup generators should have started, but their control logic sensed voltage on the wrong side of an open breaker and concluded a healthy power source was still available. Batteries good for about five minutes ran dry, and the zone went dark.

Then the trouble spread. As customers' workloads failed over to the region's other two zones, those zones slowed and returned errors. The main impact lasted about six hours, though some databases took longer to recover. Google found no impact outside the region.

Google says it has load tested its generators, reconfigured the control logic and frozen similar maintenance while it reviews comparable sites.